AC2618

UniversalModule 2AO(C) IP65

AS-Interface universal module

AC2618

UniversalModule 2AO(C) IP65

  • Easy to mount and wire
  • For the connection of sensors and actuators with cable entry
  • Device connection with cage clamps
  • Clearly visible powerful LEDs for displaying operation, switching status and error
  • ce
  • ukca
  • asib
Application
Application field installation
Electrical data
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 140
Reverse polarity protection yes
Additional voltage supply [V] 24...30 DC; (AUX)
Additional voltage supply optional
Max. current consumption from additional supply [mA] 550; (AUX)
Inputs / outputs
Number of inputs and outputs Number of analogue outputs: 2
Inputs
Precision analogue input [%] 0,5
Outputs
Number of analogue outputs 2; (connection of 2-wire or 4-wire actuators)
Analogue current output [mA] 0...20
Max. load [Ω] 600
Overload protection yes
Resolution of analogue output 16 (1 bit = 1 µA)
Actuator supply outputs AS-i / AUX
Operating conditions
Ambient temperature [°C] 0...70
Storage temperature [°C] -25...85
Max. relative air humidity [%] 90; (non condensing)
Max. height above sea level [m] 2000
Protection IP 65
Tests / approvals
EMC
EN 50295
MTTF [years] 145
AS-i classification
AS-i master profile M3; M4
AS-i profile S-7.3.5
AS-i I/O configuration [hex] 7
AS-i ID code [hex] 3.5
Mechanical data
Weight [g] 296.2
Type of mounting AS-i interface to FC-E lower parts
Materials PBT
Displays / operating elements
Display
analogue signal LED, yellow channels AO1...AO2
operation LED, green AS-i, AUX
errors LED, red
Electrical connection
Module connection Flat cables
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection cage clamps: