You probably do not come from: Australia. If necessary, change to: United States
  1. Products
  2. Industrial communication
  3. AS-Interface I/O modules
  4. Installation in control cabinets
  5. AC2258

AS-Interface control cabinet module

AC2258

SmartL50 4DI 4DO R C

AS-Interface control cabinet module

AC2258

SmartL50 4DI 4DO R C

  • For use in control cabinets
  • Simple and fast wiring by means of cage clamps
  • Particularly space-saving design
  • Double terminals for looping through the voltage supply
  • Clearly visible powerful LEDs for displaying operation, switching status and function
  • ce
  • ukca
  • asib
  • cruus
Application
Application Installation in control cabinets
Electrical data
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 300
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 4; Number of relay outputs: 4
Inputs
Number of digital inputs 4
Input circuit of digital inputs PNP; (type 2 according to IEC 61131-2)
Sensor supply of the inputs AS-i
Power supply [V] 18...30; (DC)
Max. total current rating of inputs [mA] 200
Input current High [mA] 6...10
Input current Low [mA] 0...2
Switching level high [V] > 11
Digital inputs protected against short circuits yes
Outputs
Voltage range DC [V] 24; (All outputs have to be supplied with the same voltage.: 2 x 24 V DC)
Voltage range AC [V] 10...240; (All outputs have to be supplied with the same voltage.: 2 x 240 V AC, same phase conductor)
Max. current load per output [mA] 6000; (ohmic resistance)
Max. current load outputs total [A] 6; (240 V AC; 24 V DC; ohmic resistance)
Number of relay outputs 4
Short-circuit proof no
Electrically separated yes
Operating conditions
Ambient temperature [°C] -25...60
Max. relative air humidity [%] 90; (non condensing)
Max. height above sea level [m] 2000
Protection IP 20
Pollution degree 2
Tests / approvals
EMC
EN 61000-6-2
EN 62026-2
EN 50581
MTTF [years] 279
AS-i classification
AS-i version 2.11; 3.0
AS-i addressing addressing socket
Extended addressing mode no
AS-i master profile M2; M3; M4
AS-i profile S-7.0.E
AS-i I/O configuration [hex] 7
AS-i ID code [hex] 0.E
Assignment of the data bits
data bit D0 D1 D2 D3
input I-1 I-2 I-3 I-4
Output O-1 O-2 O-3 O-4
Mechanical data
Weight [g] 275.7
Type of mounting mounting on DIN rail
Materials PA
Displays / operating elements
Display
switching status LED, yellow I1...I4, O1....O4
operation LED, green AS-i
errors LED, red
Accessories
Accessories (optional)
connectors
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection pin header: