Product characteristics |
Number of inputs and outputs |
Number of analogue outputs: 1 |
Measuring range |
-50...300 °C |
-58...572 °F |
|
Application |
Special feature |
Gold-plated contacts |
Application |
for Pt100 and Pt1000 measuring elements |
Electrical data |
Operating voltage [V] |
20...32 DC |
Protection class |
III |
Reverse polarity protection |
yes |
Power-on delay time [s] |
1 |
Integrated watchdog |
yes |
Inputs / outputs |
Number of inputs and outputs |
Number of analogue outputs: 1 |
Outputs |
Total number of outputs |
1 |
Output signal |
analogue signal; IO-Link; (configurable) |
Number of analogue outputs |
1 |
Analogue current output [mA] |
4...20 |
Max. load [Ω] |
300 |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Overload protection |
yes |
Measuring/setting range |
Measuring range |
-50...300 °C |
-58...572 °F |
|
Factory setting |
0...100 °C |
Accuracy / deviations |
Precision analogue output [K] |
± 0,3 + (± 0,1 % MS) |
Temperature coefficient [% of the span / 10 K] |
0,1 |
Response times |
Max. measuring/display cycle [ms] |
100 |
Interfaces |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.0 |
Operating conditions |
Ambient temperature [°C] |
-25...70 |
Storage temperature [°C] |
-40...85 |
Protection |
IP 67 |
Tests / approvals |
EMC |
|
Shock resistance |
DIN IEC 68-2-27 |
50 g (11 ms) |
|
Vibration resistance |
DIN IEC 68-2-6 |
20 g (10...2000 Hz) |
|
MTTF [years] |
449 |
Mechanical data |
Weight [g] |
41 |
Dimensions [mm] |
M12 x 1 |
Thread designation |
M12 x 1 |
Materials |
PA; PET; Sealing: FKM; Lock nut: stainless steel (1.4404 / 316L); plug: TPU |
Material nut |
stainless steel (1.4404 / 316L) |
Remarks |
Remarks |
operating voltage "supply class 2" according to cULus |
MS = set measuring span |
|
Pack quantity |
1 pcs. |
Electrical connection |
Connection |