SI5010 | |
SID10ADBFPKG/US-100 | Flow sensors |
SI5010 - Drawing~Print scale drawing~
![]() | |
1: LED display 2: setting pushbutton 3: internal thread M18 x 1.5 tightening torque 25 Nm | |
![]() ![]() ![]() ![]() ![]() |
Product characteristics | ||||||||
Flow monitor | ||||||||
Compact type for adapter | ||||||||
Process connection: internal thread M18 x 1.5 for adapter | ||||||||
Pressure rating: 300 bar | ||||||||
Setting range: 3...300 cm/s (liquids) | ||||||||
Application | ||||||||
Application | liquids and gases | |||||||
Pressure rating [bar] | 300 | |||||||
Medium temperature [°C] | -25...80 | |||||||
Electrical data | ||||||||
Electrical design | DC PNP | |||||||
Operating voltage [V] | 18...36 DC | |||||||
Current consumption [mA] | < 60 | |||||||
Protection class | III | |||||||
Reverse polarity protection | yes | |||||||
Outputs | ||||||||
Output function | normally open / closed programmable | |||||||
Current rating [mA] | 250 | |||||||
Voltage drop [V] | < 2.5 | |||||||
Short-circuit protection | yes (non-latching) | |||||||
Overload protection | yes | |||||||
Measuring / setting range | ||||||||
Liquids | ||||||||
Setting range [cm/s] | 3...300 | |||||||
Greatest sensitivity [cm/s] | 3...100 | |||||||
Gases | ||||||||
Setting range [cm/s] | 200...3000 | |||||||
Greatest sensitivity [cm/s] | 200...800 | |||||||
Accuracy / deviations | ||||||||
Switch point accuracy [cm/s] | ± 2...± 10 *) | |||||||
Hysteresis [cm/s] | 2...5 *) | |||||||
Repeatability [cm/s] | 1...5 *) | |||||||
Temperature drift [cm/s x 1/K] | 0.1 **) | |||||||
Max. temperature gradient of medium [K/min] | 300 | |||||||
Response times | ||||||||
Power-on delay time [s] | 10 | |||||||
Response time [s] | 1...2 ***) / 1...10 ****) | |||||||
Software / programming | ||||||||
Adjustment of the switch point | pushbuttons | |||||||
Interfaces | ||||||||
IO-Link Device | ||||||||
Transfer type | COM2 (38.4 kBaud) | |||||||
IO-Link revision | 1.1 | |||||||
SDCI standard | IEC 61131-9 | |||||||
IO-Link Device ID | 54 d / 00 00 36 h | |||||||
Profiles | Smart Sensor: Process Data Variable; Device Identification | |||||||
SIO mode | yes | |||||||
Required master port class | A | |||||||
Process data analogue | 2 | |||||||
Process data binary | 2 | |||||||
Min. process cycle time [ms] | 3.0 | |||||||
Environment | ||||||||
MAWP (for applications according to CRN) [bar] | 208 | |||||||
Ambient temperature [°C] | -25...80 | |||||||
Storage temperature [°C] | -25...100 | |||||||
Protection | IP 65 / IP 67 | |||||||
Tests / approvals | ||||||||
EMC |
| |||||||
Shock resistance |
| |||||||
Vibration resistance |
| |||||||
MTTF [Years] | 298 | |||||||
Mechanical data | ||||||||
Process connection | internal thread M18 x 1.5 for adapter | |||||||
Materials (wetted parts) | stainless steel 316L / 1.4404; O-ring: FKM 8 x 1.5 gr 80° Shore A | |||||||
Housing materials | stainless steel 316L / 1.4404; stainless steel (304S15); PC (polycarbonate); PBT-GF 20; EPDM/X | |||||||
Weight [kg] | 0.235 | |||||||
Displays / operating elements | ||||||||
Function display LED | 10 LEDs, three-colour | |||||||
Electrical connection | ||||||||
Connection | M12 connector | |||||||
Wiring SI5010 - Wiring~Print wiring diagram~
| ||||||||
Remarks | ||||||||
Remarks |
| |||||||
Pack quantity [piece] | 1 | |||||||
ifm efector, inc. • 1100 Atwater Drive • Malvern • PA 19355 We reserve the right to make technical alterations without prior notice. US SI5010 09.07.2013 |
../acgroup/SI5010.jp
Bitte warten... / please wait...

../install/SI5010.jp
Bitte warten... / please wait...

../cad/SI5010.jp
Bitte warten... / please wait...

../misc/SI5010.jp
Bitte warten... / please wait...

SI5010 - data sheet~Print data sheet~PDF data sheet~http://tds.ifm-electronic.com/tentacle/servlet/PdfRequestServlet?styleId=datasheet2_xhtml&partNumber=SI5010&pg=300&site=us&lang=ENUS&locale=en_US
SI5010 - Variants~~