SD6101

|‌ SDN12DGXFPKG/US-100

Flow sensors

DrawingWiring3D PDF PDF data sheet   Print Version

Collapse all categories
1: 4-digit alphanumeric display
2: Programming buttons
Product characteristics
Flow rate meter for gases
Quick disconnect
Process connection: ½" NPT (DN15)
Function programmable
2 outputs
OUT1 = flow monitoring (binary), flow rate meter (pulse), preset meter (binary)
OUT2 = flow monitoring (analog or binary)
Application
Application argon (Ar), carbon dioxide (CO2), nitrogen (N2)
Pressure rating [psi]232
MAWP (for applications according to CRN) [bar]16
Medium temperature [°F]32...140
Electrical data
Electrical design DC PNP
Operating voltage [V]18...30 DC *)
Current consumption [mA]< 100
Protection class III
Reverse polarity protection yes
Outputs
Output function OUT1: normally open / closed programmable or pulse
OUT2: normally open / closed programmable or analog (4...20 mA scaleable)
Current rating [mA]2 x 250
Voltage drop [V]< 2
Short-circuit protection yes (non-latching)
Overload protection yes
Analog output 4...20 mA
Max. load [Ω]< 500
Pulse output consumed quantity meter
Measuring / setting range
Flow monitoring
Measuring range [ scfh]
N2: 10...2650
Ar: 15...4310
CO2: 10...2640
[ scfm]
N2: 0.15...44.15
Ar: 0.2...71.8
CO2: 0.15...44
[ sfs]
N2: 1...339.5
Ar: 2...552
CO2: 1...338.5
Display range [ scfh]
N2: 0...3175
Ar: 0...5170
CO2: 0...3170
[ scfm]
N2: 0...52.95
Ar: 0...86.2
CO2: 0...52.8
[ sfs]
N2: 0...407.5
Ar: 0...663
CO2: 0...406
Resolution [ scfh]
N2: 5
Ar: 5
CO2: 5
[ scfm]
N2: 0.05
Ar: 0.1
CO2: 0.05
[ sfs]
N2: 0.5
Ar: 1
CO2: 0.5
Set point, SP [ scfh]
N2: 25...2650
Ar: 40...4310
CO2: 25...2640
[ scfm]
N2: 0.4...44.15
Ar: 0.7...71.8
CO2: 0.4...44
[ sfs]
N2: 3...339.5
Ar: 5...552
CO2: 3...338.5
Reset point, rP [ scfh]
N2: 15...2635
Ar: 20...4290
CO2: 15...2630
[ scfm]
N2: 0.2...43.95
Ar: 0.4...71.5
CO2: 0.2...43.8
[ sfs]
N2: 1.5...338
Ar: 3...550
CO2: 1.5...337
Analog start point, ASP [ scfh]
N2: 0...2120
Ar: 0...3445
CO2: 0...2110
[ scfm]
N2: 0...35.3
Ar: 0...57.4
CO2: 0...35.2
[ sfs]
N2: 0...271.5
Ar: 0...442
CO2: 0...271
Analog end point, AEP [ scfh]
N2: 530...2650
Ar: 860...4310
CO2: 530...2640
[ scfm]
N2: 8.85...44.15
Ar: 14.4...71.8
CO2: 8.8...44
[ sfs]
N2: 68...339.5
Ar: 110...552
CO2: 67.5...338.5
Low flow cut-off, LFC 8...46 scfh0.14...0.76 scfm1...5.8 sfs
in steps of [ scfh]
N2: 5
Ar: 5
CO2: 5
[ scfm]
N2: 0.05
Ar: 0.1
CO2: 0.05
[ sfs]
N2: 0.5
Ar: 1
CO2: 0.5
Measuring dynamics 1:300
Volumetric flow quantity monitoring
Pulse value 0.040...4 000 000 scf
in steps of 0.020...1000 scf
Pulse length [s]0.007...2
Temperature monitoring
Measuring range [°F]32...140
Display range [°F]10.5...161.5
Resolution [°F]0.5
Set point, SP [°F]32.5...140
Reset point, rP [°F]32.0...139.5
Analog start point, ASP [°F]32.0...118.5
Analog end point, AEP [°F]53.5...140
in steps of [°F]0.5
Accuracy / deviations
Flow monitoring
Accuracy ± (6% MW + 0.6% MEW) ***)
Repeatability [% of the measured value]± 1.5
Temperature monitoring
Accuracy [K]± 2 **)
Reaction times
Power-on delay time [s]1
Flow monitoring
Response time [s]< 0.1 (dAP = 0)
Damping, dAP [s]0 - 0.2 - 0.4 - 0.6 - 0.8 - 1
Software / programming
Programming options hysteresis / window function; NO / NC; current / pulse output; display can be rotated / deactivated; display unit, medium
Interfaces
IO-Link Device
Transfer type COM2
IO-Link revision 1.1
SDCI standard IEC 61131-9
IO-Link Device ID 266 d / 00 01 0a h
Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode yes
Required master port class A
Process data analogue 3
Process data binary 2
Min. process cycle time [ms]4.1
Environment
Ambient temperature [°F]32...140
Storage temperature [°F]-4...185
Max. relative air humidity [%]90
Protection IP 65
Tests / approvals
Pressure equipment directive article 3, section 3 - sound engineering practice
EMC
EN 61000-4-2 ESD:  4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated:  10 V/m
EN 61000-4-4 Burst:  2 kV
EN 61000-4-6 HF conducted:  10 V
Vibration resistance
DIN IEC 68-2-6: 5 g (55...2000 Hz)  
MTTF [Years]227
Mechanical data
Process connection ½" NPT (DN15)
Materials (wetted parts) stainless steel (304S15); ceramics glass passivated; PEEK (polyether ether ketone); polyester; Viton; aluminum anodized
Housing materials PBT-GF 20; PC (APEC); Makrolon; stainless steel (304S15); Viton
Weight [kg]1.151
Displays / operating elements
Display
Display unit  4 x LED green (scfm, scfh, scf, °F)
Function display  1 x LED yellow
Switching status  2 x LED yellow
Measured values  4-digit alphanumeric display
Programming  4-digit alphanumeric display
Electrical connection
Connection M12 connector
Wiring

Programming of the output function
----------OUT1----------
- Switching output
Hno = hysteresis / normally open
Hnc = hysteresis / normally closed
Fno = window function / normally
open
Fnc = window function / normally
closed
- ImP = pulse output for flow rate
meter / signal output
for preset meter
----------OUT2----------
- Switching output
Hno = hysteresis / normally open
Hnc = hysteresis / normally closed
Fno = window function / normally
open
Fnc = window function / normally
closed
- Analog output
I = current output (4...20 mA)
Remarks
Remarks
*) to EN50178, SELV, PELV
**) medium flow in the limit area of the flow measurement range
***) under conditions acc. to DIN ISO 2533
and when installed in DN15 pipes
MW = measured value
MEW = final value of the measuring range
Measuring, display and setting ranges refer to standard volume flow according to DIN ISO 2533.
Pack quantity [piece]1
ifm efector, inc. • 1100 Atwater Drive • Malvern • PA 19355  —  We reserve the right to make technical alterations without prior notice.  —  US  —  SD6101  —  13.05.2015
 